Modbus configuration
Modbus configuration is made directly on the panel, using the graphic interface.
Default settings:
| MODBUS SLAVE ID |
10 |
| BAUDRATE |
115200 |
| PARITY |
NONE |
| STOP BITS |
1 |
Configuration of Modbus parameters:
|
1
|
Press and hold down the button labeled "CONFIG BUTTON" on the back of the device for about 10 seconds.
The device must be in normal operation (powered on, displaying the user interface).
|
 |
|
2
|
An alarm will sound when the Modbus configuration menu is displayed. It can be muted by pressing any button, e.g. up arrow.
Navigation:
- parameter selection - up / down arrows
- parameter change - right / left arrows
Function buttons at the bottom of the screen:
| BACK |
exiting the configuration menu WITHOUT SAVING THEM |
| DEFAULTS |
load the default settings WITHOUT SAVING THEM |
| RESTART |
"soft" (software) device restart |
| SAVE |
save changes |
|
 |
| 3 |
In the upper part of the window, information about:
| SW |
the current version of the panel firmware |
| HW |
the hardware version of the panel |
| BL |
version of the firmware update module |
ATTENTION:
- This information is useful when contacting technical support.
- This information is also available via Modbus. They are in the diagnostic space.
There are settings at the bottom of the screen:
| LABEL |
DESCRIPTION |
RANGE/ POSSIBLE VALUES |
DEFAULT VALUE |
| MODBUS SLAVE ID |
Modbus device address |
1 .. 247 |
10 |
| BAUDRATE |
|
1200 2400 4800 9600 14400 19200 38400 57600 115200 230400 460800 |
115200 |
| PARITY |
|
NONE, ODD, EVEN |
NONE |
| STOP BITS |
|
1, 2 |
1 |
ATTENTION:
- The changes do not require a device reset.
- Changes are not saved automatically. Save them using the "SAVE" button. After saving, a confirmation message is displayed.
|